Gas Refilling
Gas Refilling
As SF Yangın, we provide installation, maintenance, and refilling services for automatic gas fire suppression systems designed to protect high-value equipment, data centers, electrical panels, and other critical areas. These systems ensure rapid fire extinguishing without water, minimizing damage in sensitive environments.
Safety and Periodic Maintenance of Gas Suppression Systems
Gas fire suppression systems are classified as pressure vessels and must undergo regular inspections in accordance with relevant regulations:
- Hydrostatic pressure tests are required every 10 years
- Expired pressure vessels must be tested and refilled
- Systems must be refilled after any fire discharge event
- Cylinders older than 5 years from manufacturing date must undergo pressure testing
Technical Inspection and Safety Procedures
During refilling and maintenance operations, detailed safety checks are performed:
- Valve seals (gaskets) are inspected and replaced if necessary
- “Burst disc” components are checked and replaced when required
- Solenoid valves are tested with 24V DC activation
- In detonator-based systems, current values are measured using a multimeter
- Detonators are replaced annually in applicable systems
Cylinders are pressurized with nitrogen gas and tested for leaks. All connection points are checked using sensitive leak detection methods. The system is monitored for at least 48 hours to ensure there is no pressure loss before final approval.
Refilling and Quality Control Process
At SF Yangın refilling facilities:
- Air conditioning and ventilation conditions are strictly controlled
- Precision weighing and level measurement systems are used
- Suppression agents are filled according to technical standards
- Cylinder pressure is adjusted to label specifications
- Final system tests are completed before delivery
Proper pressure control is critical, especially for agents such as FM-200 (HFC-227ea), where over-pressurization may lead to unsafe conditions.
Fire Suppression Systems We Service
SF Yangın provides refilling and maintenance services for the following systems:
- FM-200 (HFC-227ea) fire suppression systems
- Novec 1230 (FK-5-1-12) systems
- IG-01 Argon gas suppression systems
- IG-50 Nitrogen/Argon mixture systems
- IG-451 Inergen systems
- CO₂ fire suppression systems
- Panel-mounted FM-200 systems
- Panel-mounted Novec 1230 systems
- Panel-mounted dry chemical powder (DCP) systems
- Vehicle-mounted dry chemical powder systems
- Kitchen hood fire suppression systems
Professional Fire Protection You Can Trust
SF Yangın delivers more than installation—we provide engineering-based inspection, testing, maintenance, and refilling services for gas suppression systems. Our goal is to ensure continuous protection and maximum reliability for your critical assets.